Common Questions Asked About The 
QUESTION: Can
you use the MEG-ALERT on A.C. and D.C. motors?
ANSWER: Yes, the MEG-ALERT is designed to test both
A.C. and D.C. equipment
QUESTION: Can you use the
MEG-ALERT on synchronous motors?
ANSWER: Yes, the brush less type synchronous motors
will only require (1) MEG-ALERT. The brush type synchronous
motors can use (2) MEG-ALERTS, one on the stator and one on
the field.
QUESTION: Can you use the
MEG-ALERT on motors when they are running?
ANSWER: No, The MEG-ALERT is designed to test equipment
that is not in operation and prevent an insulation failure
on start up.
QUESTION: We have lightning
arrestors and power factor correction capacitors in our motor
control centers. Can we still use the MEG-ALERT?
ANSWER: Yes, providing that there are no direct grounds
on the motor side of these components. A time delay is built
into the MEG-ALERT systems to allow for some charging effects
in such cases.
QUESTION: Can I use more than
one test voltage per MEG-ALERT?
ANSWER: No, the MEG-ALERT can only provide one test
voltage value per unit.
QUESTION: Where is the MEG-ALERT
normally located in a typical circuit?
ANSWER: The MEG-ALERT in connected to the "B" phase,
at the motor contactor or generator breaker and to the equipment
ground, and is generally mounted in or next to the motor control
center or generator switchgear.
QUESTION: Can you automatically
test the insulation resistance for submersible pumps?
ANSWER: Yes, the MEG-ALERT will check submersible pumps
and the underwater cables from the starter to the motor.
QUESTION: Can you automatically
test the insulation resistance on grounded generator Systems?
ANSWER: Yes, by installing our ground interrupter on
each grounded generator equipped with a MEG-ALERT, to remove
all grounds before automatically testing insulation resistance.
Two safety circuits are provided to ensure that the ground
is re-connected before the generator can produce voltage.
QUESTION: My motors run 24
hours a day. How can MEG-ALERT benefit me?
ANSWER: Most equipment that operates 24 hours a day
is critical and can not afford lengthy downtime, however preventative
maintenance testing is required. The MEG-ALERT allows you
to perform your PM test with the minimal amount of downtime
and expense and can be done quickly during any normal interruption
that may occur with that type of equipment.
QUESTION: Can you user the
MEG-ALERT as a manual system?
ANSWER: Yes, the single MEG-ALERT units can be equipped
with a push button test feature to eliminate the auto mode
or the multiple units can simply be left in the manual position.
QUESTION: Can you set multiple
set points (trip points) with one unit?
ANSWER: Yes, some models are available with two set
points: a pre-alarm and fault alarm. The first trip point
is a pre-alarm to indicate early insulation breakdown. The
second trip point is a fault alarm that indicates that corrective
measures should be taken to prevent an impending failure.
QUESTION: Can the MEG-ALERT
be used on motors or generators with low current winding heaters?
ANSWER: Yes, in some cases it may be necessary to install
an isolation transformer on the heater input voltage circuit.
QUESTION: Can you set different
alarm settings or test voltages on each motor or generator
on the multiple model MEG-ALERT?
ANSWER: No, one common alarm setting and testing voltage
is used for all test points on the multiple model MEG-ALERT.
QUESTION: Is there any deterioration
of the insulation by continuously testing at a rated voltage?
ANSWER: No, the unit will not cause an insulation breakdown
because it uses a nondestructive D.C. test voltage with current
limiting to a maximum of 350 micro amps. Our patented voltage/current
safely circuitry also protects dead grounded equipment from
being harmed.
QUESTION: Will the MEG-ALERT
harm any of the solid-state control equipment (voltage regulator,
variable frequency drive, etc.) in my generator or motor control
panel?
ANSWER: No, the MEG-ALERT tests between the "B" phase
and the ground. Thus, there is no potential for high-test
voltages on control equipment, unless they are connected between
a phase and ground. On 240 VAC generating systems, it may
be necessary to install isolating transformers to protect
control equipment.
QUESTION: On a 4160 volt system,
how are maintenance personnel protected from high voltages
at or coming from the MEG-ALERT unit?
ANSWER: The GP2500 and GP5000 MEG-ALERT systems are
fused and current limit protected, both on the output from
the MEG-ALERT and from the motor operating voltages, for personnel
safety. Remote and local "power on" LEDs are provided with
the MEG-ALERT systems as well as a latching power on/off switch
to indicate and remove power from the MEG-ALERT system.
QUESTION: How far can a motor
or generator be from the MEG-ALERT unit?
ANSWER: The MEG-ALERT can be up to 1,000 ft. from the
equipment being tested as long as the test lead is wired with
a minimum of 18 AWG wire.
QUESTION: How are maintenance
personnel made aware that the equipment is being automatically
tested by the MEG-ALERT?
ANSWER: Remote flashing LED assemblies can be mounted
on the door of the control cabinet or motor starter bucket
and warning labels are provided with the MEG-ALERT to be mounted
on the equipment as well as the switchgear doors.
QUESTION: Will
damage occur to the MEG-ALERT if the "motor run" control signal
fails and the MEG-ALERT stays in the circuit with the operating
voltage present?
ANSWER: No, the MEG-ALERT high
internal impedance protects the system and allows the test
voltage to trip out the MEG-ALERT on a fault alarm after the
service ground is detected.
|